Prefabricated substation (European type)
- The box color can be selected so as to match with the surrounding environment. The case is made of SMC, stainless steel sheet and composite board to meet different customization requirements.
- The substation base is made of galvanized box iron or cement, so it is strong in corrosion resistance.
- The top cover of the cabinet has a double-layer structure and has good heat insulation, radiation protection and ventilation effects.
- There is an automatic exhaust device on the top of transformer room to regulate the indoor temperature.
- Be applicable to the places without severe factors such as fire hazard, explosion risks, serious dirt, chemical corrosion and violent vibration, widely applied to outdoor power supply places such as cities, residential communities, hotels, hospitals, plants and mines, airports, railways and wharfs currently.
Product Details
DOWNLOAD
-
Model Description -
-
-
-
Features
- The box color can be selected so as to match with the surrounding environment. The case is made of SMC, stainless steel sheet and composite board to meet different customization requirements.
- The substation base is made of galvanized box iron or cement, so it is strong in corrosion resistance.
- The top cover of the cabinet has a double-layer structure and has good heat insulation, radiation protection and ventilation effects.
- There is an automatic exhaust device on the top of transformer room to regulate the indoor temperature.
-
Conditions of Use
- Altitude: ≤1,000m
- Wind speed: ≤35m/S (≤700pa)
- AAmbient temperature: maximum temperature: +40℃, minimum temperature: -35℃
- Relative humidity: the daily average value is ≤90%and the monthly average value is ≤95%
- Anti-vibration: the horizontal acceleration is ≤0.4m/s2
- The vertical acceleration is ≤0.15m/s2
- Gradient in the installation site: ≤3°
- Please consult with us if the parameters exceed the above conditions.
-
Technical Parameters -
Item
Unit
Technical parameters
High-voltage side
Rated voltage
kV
12
Rated insulation level
Short-duration power-frequency withstand voltage for 1min
kV
42
Lightning impulse withstand voltage
kV
75
Rated frequency
Hz
50
Rated busbar current
A
630
Rated short-time withstand current (4S)
kA
20
Rated peak withstand current
kA
50
Rated short-circuit making current
kA
50
Low-voltage side
Rated voltage of the main circuit
V
380(400)
Rated voltage of the auxiliary circuit
V
220(230)、380(400)
Rated frequency
Hz
50
Rated insulation voltage
V
660
Rated main busbar current
A
≤4000
Busbar rated short-time withstand current (1s)
kA
15、30
Rated busbar peak withstand current
kA
30、63
Power frequency test voltage
(1min)
Main circuit
V
2500
Auxiliary circuit
V
1760
Protection grade