KYN28-12 indoor metal armoring movable switch cabinet
- Sufficient air insulating distance to avoid the probability of inter-phase accident.
- The protection grade of shell is IP4X to better prevent human body and external solid from approaching to the live part and ensure personnel safety and reliable operation of equipment;
- The key parts of large current equipment is made of non-permeability magnetic material to reduce the eddy-current loss effectively.
- Power transmission of power plant and small/medium-sized power generator, power distribution of industrial and mining enterprises, power receiving and distribution of secondary substation of power system and start of large-scale high voltage electric motor.
Product Details
DOWNLOAD
-
Model Description
-
Features
- Sufficient air insulating distance to avoid the probability of inter-phase accident.
- The protection grade of shell is IP4X to better prevent human body and external solid from approaching to the live part and ensure personnel safety and reliable operation of equipment;
- The key parts of large current equipment is made of non-permeability magnetic material to reduce the eddy-current loss effectively.
-
Conditions of Use
- Ambient temperature: Maximum temperature: +40℃; Minimum temperature: -15℃
- Ambient humidity: Daily average relative humidity: ≤95%; Monthly average relative humidity: ≤90%
- Altitude: ≤1,000m
- The seismic intensity is ≤8°
-
Technical Parameters
S/N
Item
Unit
Technical parameters
1
Rated voltage
kV
12
2
Rated insulation level
Short-duration power-frequency withstand voltage for 1min
kV
42
3
Lightning impulse withstand voltage
kV
75
4
Rated frequency
Hz
50
5
Rated busbar current
A
630, 1250, 1600, 2000, 2500, 3150, 4000
6
Rated short-time withstand current (4S)
kA
20, 25, 31.5, 40, 50
7
Rated peak withstand voltage
kA
50, 63, 80, 100, 125
8
Rated short-circuit making current
kA
50, 63, 80, 100, 125
9
Protection grade
The shell is IP4X (Compartment, and when the breaker chamber door opened, it is IP2X)